Buying round FRP cooling towers in Bangladesh
A round FRP cooling tower, which the trade calls a bottle type tower, is an induced draft counterflow unit: a top fan draws air up through the fill while a rotating sprinkler spreads hot water over it. Single cells usually run from about 5 TR to 600 TR. A round FRP cooling tower supplier in Bangladesh should quote at your conditions, not the catalogue TR.
That TR is a nominal figure at the maker's own temperatures. Roptan asks each verified seller to put flow, range, approach and design wet bulb on the quote, checks for a certified thermal rating and confirms the fan motor suits the local supply. The seller erects and commissions the tower.
How to specify a round FRP cooling tower
- Flow, range and approach
- State circulating flow in m³ per hour, hot and cold water temperatures and the design wet bulb. Without all of them, two quotes cannot be compared.
- Design wet bulb
- A wet tower can only bring water towards the air's wet bulb. Take the figure from your consultant: Dhaka's mean relative humidity is about 82 to 83 percent from June to September.
- Inlet pressure for the sprinkler
- The sprinkler turns on the water's own pressure. State the pump head left at the tower inlet and ask the seller to confirm it turns at your lowest flow.
- Make-up water analysis
- Send hardness, TDS and iron. The 2009 national survey found about 70 percent of mainly groundwater sources above 0.3 mg/L iron, which fouls fill.
- Fan and motor
- Usually a direct-drive axial fan with cast aluminium blades, or FRP blades as an option. Ask for a three phase, 50 Hz motor wound for the local supply: some Indian listings give 440 V motors.
- Drift loss
- State the drift the eliminators must meet as a percentage of circulating flow. Trade figures usually run from about 0.001 to 0.02 percent.
Ratings, tests and water safety
- CTI STD-201 certified list
- The Cooling Technology Institute certifies the published thermal ratings of a maker's model line. A catalogue TR is not a certified rating, so ask whether this exact model is on CTI's list.
- CTI ATC-105 field test
- The current edition of CTI's acceptance test code checks a tower's thermal capability on site, run by a CTI licensed test agent with the owner and the maker present.
- ANSI/ASHRAE Standard 188-2021
- Sets minimum Legionella risk management requirements for building water systems. Ask how the seller's water treatment plan and handover meet it.
Lead times and delivery
No fixed lead time can be given. It is shorter when the cell size is already built, and longer when the tower is made to order, imported and cleared at Chattogram or Benapole, fitted with hot water fill, tested on site or lifted onto a roof. A single tower is usually a normal order. Roptan confirms the dates and the minimum in the quote.
Roptan delivers the cell to your site anywhere in Bangladesh. The seller sets it level, connects the pipework, checks that the sprinkler wets all the fill, checks fan rotation and motor current, and records a test run. You receive drawings, the selection sheet, the O&M manual, the warranty and a VAT invoice (Mushak 6.3).
Questions buyers ask
What size of round tower do I need for a 100 TR chiller?
More than 100 TR of heat. The tower rejects the chiller's cooling plus the compressor's heat, about 15,000 Btu per hour per chiller ton against 12,000 for a refrigeration ton. Send the condenser water flow and temperatures, and sellers select at your design wet bulb.
Why has the sprinkler on my round tower stopped turning?
Usually because inlet pressure or flow has dropped: the head turns on the water's own force, so anything that cuts pressure at the inlet slows it, and fill the sprinkler no longer reaches stays dry and stops cooling. Measure pressure and flow at the inlet before changing parts, and ask the seller what head the sprinkler needs.
Does a round tower need water treatment?
Yes. As water evaporates the dissolved solids stay behind, and too many cycles of concentration cause scale and corrosion. Groundwater make-up usually tends to scale. The seller should set bleed-off, dosing and biocide from your make-up water analysis.
Can you supply spare fill or a sprinkler for my existing round tower?
Yes. Tower makers usually sell fill, drift eliminators, sprinkler heads and nozzles as spares. Send the nameplate, cell diameter, fill height and a photo of the sprinkler, and we source matching parts from a verified seller for a planned shutdown.
How soon will I hear back about cooling towers?
Within 48 hours of a complete requirement, with a price and a delivery date. A requirement is complete when it has the capacity, where it is needed and by when.
Who do I deal with?
With Roptan, when Roptan manages the order: we buy from the verified seller and deliver to you. With the supplier directly, when you post on the requirement board and choose a quote yourself.