- Runtime at your load
- Lead-acid is rated at slow 5-hour or 20-hour rates and gives substantially less in a fast discharge. Ask for the runtime table at your load in kW, not an Ah figure.
- String voltage and block count
- Take the DC voltage from the UPS model. IEC 62040-3 and IEC 62485-2 both stop at 1,500 V DC, so a long series string must stay within that.
- Float voltage
- Large stationary lead-acid cells typically float at about 2.25 V a cell at 25 °C. The string figure is that times the cells in series; set the charger to it.
- Temperature sensor
- Ask for temperature-compensated charging with a sensor on the string. Makers advise a lower float voltage once the room passes 29 °C; without the sensor the charger overcharges in a hot room.
- Room temperature
- Lead-acid life falls roughly by half in a room held well above 25 °C, and summer maximums here usually reach 38 to 41 °C. Plan a cooled room or cabinet.
- One string or several
- A defective battery in one parallel string can drag down good or new batteries in the others. Prefer fewer strings, or a separate charger for each series string.
- Recharge between cuts
- Lead-acid should be fully recharged soon after each discharge. Say how long and how often cuts run, so the charger is sized to refill the string before the next one.